Troubleshooting Guide.
During Limit Set Up, Gate Moves to Fully Closed Position and Does Not Return.
Possible causes: Battery low or disconnected DOSS faulty or disconnected Loose motor wires or blown motor fuse Loose battery connection Possible solutions: Check that battery voltage stay above 11.0v while gate is running Check motor wires are ...
During Limit Set Up, Gate Doesn't Run but Relay Energises. (Status Flashes 5 Times And L2 Comes on)
Possible causes: Battery low or disconnected DOSS faulty or disconnected Loose motor wires or blown motor fuse Loose battery connection Possible solutions: Check that battery voltage stay above 11.0v while gate is running Check motor wires are ...
Gate Does not Trigger (Using test or pushbutton)
Possible causes: LCK input activated Latched input on TRG or FRX input IRB input activated Faulty controller Multiple collision Battery low condition Possible solutions: Check state of LCK light must be on - if not bridge LCK to COM Check state ...
Gate Opens by Itself
Possible causes: Permanent trigger input Faulty receiver Possible solutions: Check for latched receiver or latched house pushbutton. Check if TRG light is on for a permanent trigger Intermittent fault on pushbutton line (underground joint with ...
Gate Does not Run, but Relay Energises When Unit is Activated
Possible causes: Faulty motor circuit (Master, Slave) Faulty motor relay / FET Motor fuse blown (replace with 16/20A slow blow 5x20mm) Fuse holder making bad contact. Worn motor brushes Loose motor wire Faulty controller Possible solutions: Check ...
Gate Overruns Its Limits
MASTER MOTOR: Make sure the Master Sensor plug is in properly. Check if the origin sensor is inserted properly (casing and three way plug) Make sure that the slide cover over the manual release is swiveled back. Check if the origin was moved. If in ...
Gate Runs a Short Distance and Stops - (Status flashing 4 times)
Possible causes: Multiple collision condition Incorrect or loose wiring Loose fuse Sensor unplugged or faulty Possible solutions: Adjust collision sensitivity (high to medium or to low) Check for something physically obstructing the movement of ...
Gate Runs a Short Distance and Stops (Status flashing 3 times)
Possible causes: Battery low condition (Status flashing 3 times) Old battery Possible solutions: Check battery charger Check that the charge voltage is 13.7V with no battery connected Charge rate (Check recovery rate of charger) Check duty cycle of ...