Possible causes
• The operator is encountering an obstruction and has reached the pre-set number of allowable collisions
• The controller collision force is set too sensitively
• Number of allowable collisions set to a low value, e.g. 1
• Excessive wind loading
• Damaged encoder
• The operators in a double-leaf installation are different versions, resulting in excess current draw from one operator’s encoder sensor
• Dimensions for A, B, and C are incorrect
• Faulty DOSS harness. Repair work of this nature should be conducted by a qualified technician
• Loose drive and/or sensor connections
•
Gearbox not fully engaged
Solutions
• Ensure that the gate is running smoothly and that there is nothing physically hindering the trajectory of the gate
• Increase the collision force (Menu 2: Safety)
• Increase maximum collisions value to a higher number, typically 4
• Ensure A, B, and C dimensions are correct
• Ensure that both operators in a double leaf installation are the same version (e.g. v2 - VECTOR2)
• Replace faulty DOSS harness. Repair work of this nature should be conducted by a qualified technician
• Check battery, motor terminal and sensor connections; check connections on the controller at any junction points between the operator and the controller
• Ensure that operator is fully engaged by turning the key fully clockwise
• Replace faulty DOSS encoder. Repair work of this nature should be conducted by a qualified technician
• As the encoder is mounted inside the actuator, it is preferable to replace the actuator