Gate Runs a Short Distance and Stops

Gate Runs a Short Distance and Stops

Possible causes: 

Battery low condition

Multiple collision condition

Collision sensing too sensitive

Faulty motor assembly

Faulty controller

Faulty or disconnected DOSS


Possible solutions: 

Measure battery voltage under static and load conditions as per the procedure described later. Replace if necessary

Ensure that duty cycle is not exceeded (10 operations per day)

Clean any corrosive build-up around the battery terminals

Check for something physically obstructing the movement of the gate or set the sensitivity from High to Medium or Low

nsure that the DOSS is plugged in on the controller and encoder side.

Bring in the motor for testing at your closest CENTURION branch as the motor assembly, controller or DOSS might be faulty



    • Related Articles

    • Gate Runs a Short Distance and Stops - (Status flashing 4 times)

      Possible causes:  Multiple collision condition  Incorrect or loose wiring Loose fuse Sensor unplugged or faulty   Possible solutions:  Adjust collision sensitivity (high to medium or to low) Check for something physically obstructing the movement of ...
    • Set Up Fail: No End Stops Found (D-Series)

      Possible Causes • Mechanical Endstops have not been installed • Oil in DOSS chamber • DOSS faulty or disconnected • Electric fence contact preventing gate from reaching fully closed position • Faulty electrical motor Solutions • Install physical End ...
    • Gate Runs a Short Distance and Stops (Status flashing 3 times)

      Possible causes:  Battery low condition (Status flashing 3 times) Old battery Possible solutions:  Check battery charger Check that the charge voltage is 13.7V with no battery connected Charge rate (Check recovery rate of charger) Check duty cycle of ...
    • How to determine if there's an oil leak on the D5 Evo Sliding gate motor

      If you your gate is running a short distance and stop or slams into the ends stoppers, and your controller LCD screen is displaying either a ""gate stalled"", ""Motor fault"" or "" Max collision"" error, kindly refer to the below steps: Symptom: ...
    • Set Up Fail: No End Stops Found (D-Series)

      Possible Causes • Mechanical Endstops have not been installed • DOSS faulty or disconnected • Electric fence contact preventing gate from reaching fully closed position • Faulty electrical motor Solutions • Install physical End stops in order to ...