Gate Does not Move at all (three short beeps)

Gate Does not Move at all (three short beeps)

Possible causes: 

Poor connection between battery and controller

The battery voltage is low or the battery is faulty or disconnected

There is no mains power to the motor

Faulty controller 


Possible solutions: 

Ensure that the battery terminals are properly connected on both the controller and battery side

Measure the battery voltage – it should be no lower than 11V DC when placed under load.

Check for corrosive build-up around the battery terminals. If there is corrosion, replace both the battery and terminals

Replace the battery

Measure the onboard charger’s output voltage. It should be about 14V DC

Ensure that the safety PE beams are in working order

Replace controller



    • Related Articles

    • Gate Does not Open From the Fully Closed Position (three short beeps)

      Possible causes:  Opening infrared gate safety beams incorrectly wired Opening beams faulty ​ Possible solutions:  Ensure that the beam receiver relay Com has been connected to Safe Com (Centurion photon beams only) Replace faulty infrared PE beams
    • Gate Runs a Short Distance and Stops - (Status flashing 4 times)

      Possible causes:  Multiple collision condition  Incorrect or loose wiring Loose fuse Sensor unplugged or faulty   Possible solutions:  Adjust collision sensitivity (high to medium or to low) Check for something physically obstructing the movement of ...
    • Gate Does not Move at All (five quick beeps continuously)

      Possible causes:  Poor connection between battery and controller The battery voltage is low or the battery is faulty or disconnected Poor connection between motor wires and controller Motor fuse blown DOSS physically disconnected Faulty motor and ...
    • Gate Runs a Short Distance and Stops

      Possible causes:  Battery low condition Multiple collision condition Collision sensing too sensitive Faulty motor assembly Faulty controller Faulty or disconnected DOSS Possible solutions:  Measure battery voltage under static and load conditions as ...
    • Gate Stalled (D-Series)

      Possible causes: • The operator is encountering a fixed obstruction • The operator is jammed into an Endstop • The gearbox is disengaged (D5-Evo/D5-Evo only) • Loose drive connection (battery or motor terminal) • Oil in DOSS chamber • Faulty DOSS • ...