Aux Overload (Sector)

Aux Overload (Sector)

Possible Causes
This error indication is displayed in the event of excess
current being drawn.
• Incorrect spring orientation
• Incorrect spring tension
• Too many auxiliary components connected to 12V auxiliary
output
• The maximum current that should be drawn by the SECTOR II
traffic barrier controller is 3A (momentarily) or 1A (continuous)
• One specific auxiliary device that is faulty, typically having
a short circuit
• Charging voltage significantly higher than 14V DC due to
faulty charger or controller

Solutions
• Ensure that the orientation of the spring corresponds with
the orientation of the boom pole. Refer to the SECTOR II
manual for further details
• Check the spring balance by referring to the Spring
Tension Diagnostic screen, and correct if necessary
• Ensure that the battery charging voltage is no higher than
14V DC. Refer to Appendix A on page 61 for a description
of how to test battery and charging voltages
• Disconnect and reconnect auxiliary components one by
one in order to isolate the problem

    • Related Articles

    • Aux Overload (D-Series)

      Possible causes • The maximum current that should be drawn by a D10 controller is 300mA (momentarily); 200mA (continuous) • This error indication is displayed in the event of excess current being drawn • Too many auxiliary components connected to 12V ...
    • Sector 2 Installation Manual

      Please find attached the installation manual for the Sector 2 boom barrier, which includes the following sections: Glossary of terms Product identification Physical installation Onsite electrical wiring Basic controller setup Installation handover ...
    • How do I override Auto FRX on Sector Controllers

      Wiring: Programming: 1. Under Chrono-guard menu select Auto XIO 2. Select start time and end time (Ex. Start: MTWTF 07:00, End: MTWTF 17:00) 3. Invert logic OFF 4. Remote learned in as a Latch on the receiver. Basic Operation: When XIO is active ...
    • No Limits Set (Sector)

      This error will display if the End-of-travel limits have not been established. Solution • Set the gate travel limits by accessing the Setting Limits menu (Menu1: Setting Limits) and following the onscreen prompts or steps supplied below: The ...
    • Presence Alarm (Sector)

      Possible Causes • The closing loop has been activated for the time specified in Menu 6.5.1.2: Presence Time • Inadvertent activation of the Presence Alarm feature Solutions • Remove any metal objects from the closing loop • Check the loop wiring and ...